User Manual
English
APC Smart-UPS XL 2200/3000 VA 120/230 VAC Rack Mount 3U Uninterruptible Power Supply
990-2404
06/2005
Introduction
Introduction About this UPS The APC Uninterruptible Power Supply (UPS) provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged.
Unpack Read the Safety Guide before installing the UPS. The User Manual and Safety Guide are accessible on the supplied User Manuals CD and on the APC Web site, www.apc.com. Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly. Check the package contents: • • • • •
UPS Front bezel Rail kit EPO connector UPS literature kit containing: – Two mounting brackets – Eight flathead screws – Product documentation – Smart-UPS® User Manuals CD – PowerChute® CD – Serial and USB communication cables – Safety information – Warranty information
230V Models Only: UPS literature kit additional contents: • Input power cord • Alternate input power cord (UK customers) • Utility connector plug • IEC jumper cables
The model and serial numbers for all units are located on the rear panel. See the small label with numbers and bar codes.
Specifications Temperature Operating Storage
This unit is designed for indoor
32° to 104° F (0° to 40° C) use only. Select a location sturdy 5° to 86° F (-15° to 30° C) charge the UPS battery every six months enough to handle the weight. 86° to 113° F (30° to 45° C) charge the UPS battery every three months Do not operate the UPS where
Maximum Elevation Operating Storage
10,000 ft (3,000 m) 50,000 ft (15,240 m)
Humidity
0 to 95% relative humidity, non-condensing
Weight
135 lbs (61 kg) with battery module 80 lbs (36 kg) without battery module
Maximum Number of External Battery Packs Supported by the Smart-UPS XL Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
there is excessive dust or the temperature or humidity are outside the specified limits.
135 lbs (61 kg)
10 3
Installation
Installation Your UPS model may vary from the examples depicted in this manual. The UPS and the battery module are heavy. Remove the battery module to lighten the UPS during installation.
Install the Rails in the Rack For details on rail installation refer to the instructions in the rail kit.
Install the UPS in the Rack and Connect the Battery Module
0014
0015
4x
4x
0017 0016
0018
4
0019
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Start Up
Accessories This UPS is equipped with an accessory SmartSlot. Refer to the APC Web site, www.apc.com for available accessories. If a standard accessory, such as a SNMP card is installed on this UPS, refer to the Utility CD for user documentation. Install accessories prior to connecting power to the UPS.
Start Up Connect Equipment and Power to the UPS 1. The UPS features a transient voltage surge-suppression (TVSS) screw located on the rear panel, for connecting the ground lead on surge suppression devices such as telephone and network line protectors. Prior to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery power. 2. Connect equipment to the UPS. NOTE: This UPS is equiped with an external battery connector on the rear panel of the unit. Where appropriate use an APC extension battery cable. For ordering details contact your dealer or APC through the Web site www.apc.com. 3. Add optional accessories to the SmartSlot located on the rear panel. 4. Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. – 230 V models: The utility power cord is supplied in the UPS literature kit. Prior to connecting the utility power, connect the ground lead (optional) to the TVSS screw. 5. 120 V models: Check the SITE WIRING FAULT LED located on the rear panel. The LED will be illuminated if the UPS is plugged into an improperly wired utility power outlet, (see Troubleshooting). 6. To use the UPS as a master on/off switch be sure all connected equipment is switched on.
Rear Panels 120 VAC
230 VAC
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
5
Start Up
Start the UPS 1. Press the button on the front panel to start the UPS. – The battery charges to 90% capacity during the first four hours of normal operation. Do not expect full battery run capability during this initial charge period. – Refer to the APC Web site, www.apc.com for battery runtimes. 2. For optimal computer system security, install PowerChute Smart-UPS monitoring software.
Communication Ports SERIAL PORT
USB PORT
Use only the supplied cable to connect to the serial port. A standard serial interface cable is incompatible with the UPS. Serial and USB ports cannot be used simultaneously.
Emergency Power Off The emergency power off (EPO) feature is user configurable. EPO provides immediate de-energizing of connected equipment from a remote location, without switching to battery operation. 1. Use the EPO connector supplied with the UPS. 2. Use a normally-open contact to connect the +24 terminal to the IN terminal. External voltage is not required. 3. Wire the four-pin connector to the EPO system. EPO PORT (located on rear panel)
EPO Connector
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay properly isolated from the utility. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a closure type circuit. Use one of the following cable types to connect the UPS to the EPO switch. • • • • • •
6
CL2: Class 2 cable for general use. CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air. CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft. CLEX: Limited use cable for use in dwellings and for use in raceways. For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable). For installation in other countries: Use standard low-voltage cable in accordance with national and local regulations.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Operation
Operation Display Panels 120 V models
Load
230 V models
/
Battery Charge
Display Panel Indicators and Function Buttons Indicator LED
Indicator Title
Description
On Line
The UPS is supplying utility power to the connected equipment, (see Troubleshooting).
AVR Trim
The UPS is compensating for a high utility voltage. Refer to the APC Web site, www.apc.com for AVR settings.
AVR Boost
The UPS is compensating for a low utility voltage. Refer to the APC Web site, www.apc.com for AVR settings.
On Battery
The UPS is supplying battery power to the connected equipment.
Overload
The connected equipment is drawing more than the UPS power rating allows, (see Troubleshooting).
Replace Battery/Battery The battery is disconnected or must be replaced, (see Troubleshooting). Disconnected
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
7
Operation 230V
120V
Diagnostic Utility Voltage
The UPS has a diagnostic feature that indicates the utility voltage. The UPS starts a self-test as part of this procedure. The self-test does not affect the voltage display. Press and hold the
Battery Charge
Feature Button
button to view the utility voltage bar graph indicator. After
a few seconds, this five-LED Battery Charge indicator on the right of the display panel will show the utility input voltage. Refer to the figure on the left for the voltage reading. Values are not listed on the UPS. The indicator on the UPS shows the voltage is between the displayed value on the list and the next higher value, (see Troubleshooting).
Feature Title
Function
Power On
Press this button to turn on the UPS. Continue reading for additional capabilities.
Power Off
Press this button to turn off the UPS.
Self-Test
Automatic: The UPS performs a self-test automatically when tuned on, and every two weeks thereafter (by default). During the self-test, the UPS briefly operates the connected equipment on battery. Manual: Press and hold the self-test.
Cold Start
8
button for a few seconds to initiate the
When there is no utility power and the UPS is off, the cold start feature will switch the UPS and connected equipment onto battery power, (see Troubleshooting).
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Configuration
Configuration UPS settings Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.
Function
Factory Default
User Selectable Choices
Description
Automatic Self-Test
On startup and every 14 days (336 hours) there after
• Every 7 days (168 hours) • On startup and every 14 days (336 hours) there after • On startup only • No self-test
Set the interval at which the UPS will execute a self-test.
UPS ID
UPS_IDEN
Up to eight characters (alphanumeric)
Uniquely identify the UPS, (i.e. server name or location) for network management purposes.
Date of Last Battery Replacement
Manufacture Date
mm/dd/yy
Reset this date when you replace the battery module.
Minimum Capacity Before Return from Shutdown
0 percent
• • • •
Voltage Sensitivity The UPS detects and reacts to line voltage distortions by transferring to battery operation to protect the connected equipment.
High sensitivity
Alarm Delay Control
Enable
• Enable • Mute • Disable
Shutdown Delay
90 seconds
• • • •
0% 15% 30% 45%
• 60% • 75% • 90%
Brightly illuminated: high sensitivity Dimly illuminated: medium sensitivity No illumination: low sensitivity
0s 90 s 180 s 270 s
Specify the percentage to which batteries will be charged following a low battery shutdown before powering connected equipment.
Adjust by pressing the VOLTAGE SENSITIVIY switch (rear panel). Use a pointed object, (such as a pen) to do so. Note: In situations of poor power quality, the UPS may frequently transfer to battery operation. If the connected equipment can operate normally under such conditions, reduce the sensitivity setting to conserve battery capacity and service life. Voltage sensitivity levels can be changed through PowerChute software. Mute ongoing alarms or disable all alarms permanently.
• • • •
360 s 450 s 540 s 630 s
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Set the interval between the time when the UPS receives a shutdown command and actual shutdown.
9
Configuration
Function Low Battery Warning PowerChute software interface provides automatic, unattended shutdown when approximately two minutes of battery operated run time remains.
Factory Default 2 minutes
User Selectable Choices Brightly illuminated: low battery warning level of about 2 minutes Dimly illuminated: low battery warning level of about 5 minutes No illumination: low battery warning level is about 8 minutes
The low-battery warning beeps are continuous when two minutes of run time remain. To change the default interval setting, use a pointed object such as a pen to press the
Specify the time the UPS will wait after the return of utility power before start up, (to avoid branch circuit overload).
Synchronized Turn-on Delay
0 seconds
• • • •
High Transfer Point
120 V models: 127 VAC
• 127 VAC • 130 VAC
• 133 VAC • 136 VAC
230 V models: 253 VAC
• 253 VAC • 257 VAC
• 261 VAC • 265 VAC
120 V models: 106 VAC
• 97 VAC • 100 VAC
• 103 VAC • 106 VAC
230 V models: 208 VAC
• 196 VAC • 200 VAC
• 204 VAC • 208 VAC
230 VAC
• 220 VAC
• 240 VAC
Low Transfer Point
Output Voltage 230 V models
10
Description
0s 60 s 120 s 180 s
• • • •
240 s 300 s 360 s 420 s
VOLTAGE SENSITIVIY switch panel), while
(rear
pressing the button, (front display). Change the low battery warning interval setting to the time that the operating system or system software requires to safely shut down.
To avoid unnecessary use of the battery where utility voltage is chronically high, set the high transfer point higher if the connected equipment can tolerate this condition.
To avoid unnecessary use of the battery where utility voltage is chronically low, set the low transfer point lower if the connected equipment can tolerate this condition.
230 V models only: Sets the output voltage of the UPS.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Maintenance, Transport, and Service
Maintenance, Transport, and Service Replacing the Battery Module This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the replacement procedure. Once the batteries are disconnected the connected equipment is not protected from power outages. Refer to the appropriate replacement battery user manual for battery module installation instructions. See your dealer or contact APC at www.apc.com for information on replacement battery modules. Be sure to deliver the spent battery(s) to a recycling facility or ship it to APC in the replacement battery packing material.
Service If the UPS requires service do not return it to the dealer. Follow these steps: 1. Review the problems discussed in Troubleshooting to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com. – Note the model number of the UPS, the serial number located on the back of the unit, and the date purchased. If you call APC Customer Support, a technician will ask you to describe the problem and attempt to solve it over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#). – If the UPS is under warranty, repairs are free. – Procedures for servicing or returning products may vary internationally. Refer to the APC Web site for country specific instructions. 3. Pack the UPS in its original packaging. If this is not available, refer to www.apc.com for information about obtaining a new set. – Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging. Damage sustained in transit is not covered under warranty. – Always DISCONNECT THE UPS BATTERY before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The battery may remain in the UPS. 4. Mark the RMA# on the outside of the package. 5. Return the UPS by insured, prepaid carrier to the address given to you by Customer Support.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
11
Troubleshooting
Troubleshooting Use this chart to solve minor UPS installation and operation problems. Refer to www.apc.com for assistance with complex UPS problems. Problem and/or Possible Cause
Solution
UPS will not turn on The battery is not connected properly. button not pushed.
Check that the battery connector is fully engaged. Press the
button once to power-up the UPS and connected equipment.
The UPS is not connected to utility power supply.
Check that the power cable from the UPS to the utility power supply is securely connected at both ends.
Very low or no utility voltage
Check the utility power supply to the UPS by plugging in a table lamp. If the light is very dim, have the utility voltage checked.
UPS will not turn off The UPS is experiencing an internal fault
Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.
UPS beeps occasionally Normal UPS operation when running on battery.
None: The UPS is protecting the connected equipment. Press the to silence this alarm.
button
UPS is not providing expected backup time The UPS battery(s) are weak due to a recent power outage or battery(s) are near the end of their service life.
Charge the battery(s). Batteries require recharging after extended outages. Batteries can wear faster when put into service often or when operated at elevated temperatures. If the battery(s) are near the end of their service life, consider replacing the battery(s) even if the replace battery LED is not yet illuminated.
All LEDs are illuminated and the UPS emits a constant beeping The UPS is experiencing an internal fault.
Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.
Front panel LEDs flash sequentially The UPS has been shut down remotely through software or an optional accessory card.
None: The UPS will restart automatically when utility power returns.
All LEDs are off and the UPS is plugged into a wall outlet The UPS is shut down or the battery is discharged from an extended outage. 12
None: The UPS will restart automatically when utility power is restored and the battery has a sufficient charge. Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Troubleshooting
Problem and/or Possible Cause
Solution
The Overload LED is illuminated and the UPS emits a sustained alarm tone The UPS is overloaded.
The connected equipment exceeds the specified “maximum load” as defined in Specifications on the APC Web site, www.apc.com. The alarm remains on until the overload is removed. Disconnect nonessential equipment from the UPS to eliminate the overload condition. The UPS continues to supply power as long as it is online and the circuit breaker does not trip; the UPS will not provide power from batteries in the event of a utility voltage interruption.
The Replace Battery/Battery Disconnected LED is illuminated The Replace Battery/Battery Disconnected LED flashes and a short beep is emitted every two seconds to indicate the battery is disconnected.
Check that the battery connectors are fully engaged.
Weak battery
Allow the battery to recharge for 24 hours and perform a self-test. If the problem persists after recharging, replace the battery.
Failure of a battery self-test: Replace Battery/Battery Disconnected LED illuminates and the UPS emits short beeps for one minute. The UPS repeats the alarm every five hours.
Allow the battery to recharge for 24 hours. Perform the self-test procedure to confirm the replace battery condition. The alarm stops and the LED clears if the battery passes the self-test. If the battery fails again, it must be replaced. The connected equipment is unaffected.
The Site Wiring Fault LED on the rear panel is illuminated (120 V model only) The UPS is plugged into an improperly wired utility power outlet.
Wiring faults detected include missing ground, hot-neutral polarity reversal, and overloaded neutral circuit. Contact a qualified electrician to correct the building wiring.
The input circuit breaker trips The connected equipment exceeds the specified “maximum load” as defined in Specifications on the APC Web site, www.apc.com.
Unplug all nonessential equipment from the UPS. Reset the circuit breaker.
The AVR Boost or AVR Trim LEDs are illuminated The system is experiencing very high or low utility voltage.
Have a qualified service personnel check your facility for electrical problems. If the problem persists, contact the utility company for further assistance.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
13
Troubleshooting
Problem and/or Possible Cause
Solution
There is no utility power There is no utility power and the UPS is off.
Use the cold start feature to supply power to the connected equipment front the UPS battery(s). Press and hold the button. There will be a short beep followed by a longer beep. Release the button during the second beep.
UPS operates on battery although line voltage exists The UPS input circuit breaker trips.
Unplug all nonessential equipment from the UPS. Reset the circuit breaker.
Your system is experiencing very high, low or distorted line voltage.
Move the UPS to a different outlet on a different circuit: Inexpensive fuel powered generators may distort the voltage. Test the input voltage with the utility voltage display, (see Operation). If acceptable to the connected equipment, reduce the UPS sensitivity.
Battery Charge and Load LEDs flash simultaneously The UPS has shut down. The internal temperature of the UPS has exceeded the allowable threshold for safe operation.
Check that the room temperature is within the specified limits for operation. Check that the UPS is properly installed, allowing for adequate ventilation. Allow the UPS to cool down. Restart the UPS. If the problem persists, contact APC at www.apc.com.
Diagnostic utility voltage All five LEDs are illuminated.
The line voltage is extremely high and should be checked by an electrician.
There is no LED illumination.
The line voltage is extremely low and should be checked by an electrician.
On Line LED There is no LED illumination.
The UPS is running on battery, or it must be turned on.
The LED is blinking.
The UPS is running an internal self-test.
14
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Regulatory and Warranty Information
Regulatory and Warranty Information Regulatory Agency Approvals and Radio Frequency Warnings FCC Compliance Notice
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy. If it is not installed and used in accordance with the instruction manual, it may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case users will be required to take whatever measures may be necessary to correct the interference at their own expense.
120 V models
R3A031 LISTED 42C2 E95463
230 V models N 394
geprüf te Sich erh eit
Limited Warranty American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply to equipment that has been damaged by accident, negligence, or misapplication or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. EXCEPT AS PROVIDED HEREIN, AMERICAN POWER CONVERSION MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser. EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL APC BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, APC is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
15
Regulatory and Warranty Information
Date of product declaration
16
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Regulatory and Warranty Information
APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: •
Refer to the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. – www.apc.com/support/ Global support searching APC Knowledge Base and using e-support. • Contact an APC Customer Support center by telephone or e-mail. Local, country-specific centers: go to www.apc.com/support/contact for information. Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support.
Entire contents copyright 2005 American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited. APC, the APC logo, Smart-UPS, and PowerChute are trademarks of American Power Conversion Corporation. All other trademarks, product names, and corporate names are the property of their respective owners and are used for informational purposes only.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
17
English
APC Smart-UPS XL 2200/3000 VA 120/230 VAC Rack Mount 3U Uninterruptible Power Supply
990-2404
06/2005
Introduction
Introduction About this UPS The APC Uninterruptible Power Supply (UPS) provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged.
Unpack Read the Safety Guide before installing the UPS. The User Manual and Safety Guide are accessible on the supplied User Manuals CD and on the APC Web site, www.apc.com. Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly. Check the package contents: • • • • •
UPS Front bezel Rail kit EPO connector UPS literature kit containing: – Two mounting brackets – Eight flathead screws – Product documentation – Smart-UPS® User Manuals CD – PowerChute® CD – Serial and USB communication cables – Safety information – Warranty information
230V Models Only: UPS literature kit additional contents: • Input power cord • Alternate input power cord (UK customers) • Utility connector plug • IEC jumper cables
The model and serial numbers for all units are located on the rear panel. See the small label with numbers and bar codes.
Specifications Temperature Operating Storage
This unit is designed for indoor
32° to 104° F (0° to 40° C) use only. Select a location sturdy 5° to 86° F (-15° to 30° C) charge the UPS battery every six months enough to handle the weight. 86° to 113° F (30° to 45° C) charge the UPS battery every three months Do not operate the UPS where
Maximum Elevation Operating Storage
10,000 ft (3,000 m) 50,000 ft (15,240 m)
Humidity
0 to 95% relative humidity, non-condensing
Weight
135 lbs (61 kg) with battery module 80 lbs (36 kg) without battery module
Maximum Number of External Battery Packs Supported by the Smart-UPS XL Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
there is excessive dust or the temperature or humidity are outside the specified limits.
135 lbs (61 kg)
10 3
Installation
Installation Your UPS model may vary from the examples depicted in this manual. The UPS and the battery module are heavy. Remove the battery module to lighten the UPS during installation.
Install the Rails in the Rack For details on rail installation refer to the instructions in the rail kit.
Install the UPS in the Rack and Connect the Battery Module
0014
0015
4x
4x
0017 0016
0018
4
0019
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Start Up
Accessories This UPS is equipped with an accessory SmartSlot. Refer to the APC Web site, www.apc.com for available accessories. If a standard accessory, such as a SNMP card is installed on this UPS, refer to the Utility CD for user documentation. Install accessories prior to connecting power to the UPS.
Start Up Connect Equipment and Power to the UPS 1. The UPS features a transient voltage surge-suppression (TVSS) screw located on the rear panel, for connecting the ground lead on surge suppression devices such as telephone and network line protectors. Prior to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery power. 2. Connect equipment to the UPS. NOTE: This UPS is equiped with an external battery connector on the rear panel of the unit. Where appropriate use an APC extension battery cable. For ordering details contact your dealer or APC through the Web site www.apc.com. 3. Add optional accessories to the SmartSlot located on the rear panel. 4. Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. – 230 V models: The utility power cord is supplied in the UPS literature kit. Prior to connecting the utility power, connect the ground lead (optional) to the TVSS screw. 5. 120 V models: Check the SITE WIRING FAULT LED located on the rear panel. The LED will be illuminated if the UPS is plugged into an improperly wired utility power outlet, (see Troubleshooting). 6. To use the UPS as a master on/off switch be sure all connected equipment is switched on.
Rear Panels 120 VAC
230 VAC
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
5
Start Up
Start the UPS 1. Press the button on the front panel to start the UPS. – The battery charges to 90% capacity during the first four hours of normal operation. Do not expect full battery run capability during this initial charge period. – Refer to the APC Web site, www.apc.com for battery runtimes. 2. For optimal computer system security, install PowerChute Smart-UPS monitoring software.
Communication Ports SERIAL PORT
USB PORT
Use only the supplied cable to connect to the serial port. A standard serial interface cable is incompatible with the UPS. Serial and USB ports cannot be used simultaneously.
Emergency Power Off The emergency power off (EPO) feature is user configurable. EPO provides immediate de-energizing of connected equipment from a remote location, without switching to battery operation. 1. Use the EPO connector supplied with the UPS. 2. Use a normally-open contact to connect the +24 terminal to the IN terminal. External voltage is not required. 3. Wire the four-pin connector to the EPO system. EPO PORT (located on rear panel)
EPO Connector
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay properly isolated from the utility. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a closure type circuit. Use one of the following cable types to connect the UPS to the EPO switch. • • • • • •
6
CL2: Class 2 cable for general use. CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air. CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft. CLEX: Limited use cable for use in dwellings and for use in raceways. For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable). For installation in other countries: Use standard low-voltage cable in accordance with national and local regulations.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Operation
Operation Display Panels 120 V models
Load
230 V models
/
Battery Charge
Display Panel Indicators and Function Buttons Indicator LED
Indicator Title
Description
On Line
The UPS is supplying utility power to the connected equipment, (see Troubleshooting).
AVR Trim
The UPS is compensating for a high utility voltage. Refer to the APC Web site, www.apc.com for AVR settings.
AVR Boost
The UPS is compensating for a low utility voltage. Refer to the APC Web site, www.apc.com for AVR settings.
On Battery
The UPS is supplying battery power to the connected equipment.
Overload
The connected equipment is drawing more than the UPS power rating allows, (see Troubleshooting).
Replace Battery/Battery The battery is disconnected or must be replaced, (see Troubleshooting). Disconnected
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
7
Operation 230V
120V
Diagnostic Utility Voltage
The UPS has a diagnostic feature that indicates the utility voltage. The UPS starts a self-test as part of this procedure. The self-test does not affect the voltage display. Press and hold the
Battery Charge
Feature Button
button to view the utility voltage bar graph indicator. After
a few seconds, this five-LED Battery Charge indicator on the right of the display panel will show the utility input voltage. Refer to the figure on the left for the voltage reading. Values are not listed on the UPS. The indicator on the UPS shows the voltage is between the displayed value on the list and the next higher value, (see Troubleshooting).
Feature Title
Function
Power On
Press this button to turn on the UPS. Continue reading for additional capabilities.
Power Off
Press this button to turn off the UPS.
Self-Test
Automatic: The UPS performs a self-test automatically when tuned on, and every two weeks thereafter (by default). During the self-test, the UPS briefly operates the connected equipment on battery. Manual: Press and hold the self-test.
Cold Start
8
button for a few seconds to initiate the
When there is no utility power and the UPS is off, the cold start feature will switch the UPS and connected equipment onto battery power, (see Troubleshooting).
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Configuration
Configuration UPS settings Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.
Function
Factory Default
User Selectable Choices
Description
Automatic Self-Test
On startup and every 14 days (336 hours) there after
• Every 7 days (168 hours) • On startup and every 14 days (336 hours) there after • On startup only • No self-test
Set the interval at which the UPS will execute a self-test.
UPS ID
UPS_IDEN
Up to eight characters (alphanumeric)
Uniquely identify the UPS, (i.e. server name or location) for network management purposes.
Date of Last Battery Replacement
Manufacture Date
mm/dd/yy
Reset this date when you replace the battery module.
Minimum Capacity Before Return from Shutdown
0 percent
• • • •
Voltage Sensitivity The UPS detects and reacts to line voltage distortions by transferring to battery operation to protect the connected equipment.
High sensitivity
Alarm Delay Control
Enable
• Enable • Mute • Disable
Shutdown Delay
90 seconds
• • • •
0% 15% 30% 45%
• 60% • 75% • 90%
Brightly illuminated: high sensitivity Dimly illuminated: medium sensitivity No illumination: low sensitivity
0s 90 s 180 s 270 s
Specify the percentage to which batteries will be charged following a low battery shutdown before powering connected equipment.
Adjust by pressing the VOLTAGE SENSITIVIY switch (rear panel). Use a pointed object, (such as a pen) to do so. Note: In situations of poor power quality, the UPS may frequently transfer to battery operation. If the connected equipment can operate normally under such conditions, reduce the sensitivity setting to conserve battery capacity and service life. Voltage sensitivity levels can be changed through PowerChute software. Mute ongoing alarms or disable all alarms permanently.
• • • •
360 s 450 s 540 s 630 s
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Set the interval between the time when the UPS receives a shutdown command and actual shutdown.
9
Configuration
Function Low Battery Warning PowerChute software interface provides automatic, unattended shutdown when approximately two minutes of battery operated run time remains.
Factory Default 2 minutes
User Selectable Choices Brightly illuminated: low battery warning level of about 2 minutes Dimly illuminated: low battery warning level of about 5 minutes No illumination: low battery warning level is about 8 minutes
The low-battery warning beeps are continuous when two minutes of run time remain. To change the default interval setting, use a pointed object such as a pen to press the
Specify the time the UPS will wait after the return of utility power before start up, (to avoid branch circuit overload).
Synchronized Turn-on Delay
0 seconds
• • • •
High Transfer Point
120 V models: 127 VAC
• 127 VAC • 130 VAC
• 133 VAC • 136 VAC
230 V models: 253 VAC
• 253 VAC • 257 VAC
• 261 VAC • 265 VAC
120 V models: 106 VAC
• 97 VAC • 100 VAC
• 103 VAC • 106 VAC
230 V models: 208 VAC
• 196 VAC • 200 VAC
• 204 VAC • 208 VAC
230 VAC
• 220 VAC
• 240 VAC
Low Transfer Point
Output Voltage 230 V models
10
Description
0s 60 s 120 s 180 s
• • • •
240 s 300 s 360 s 420 s
VOLTAGE SENSITIVIY switch panel), while
(rear
pressing the button, (front display). Change the low battery warning interval setting to the time that the operating system or system software requires to safely shut down.
To avoid unnecessary use of the battery where utility voltage is chronically high, set the high transfer point higher if the connected equipment can tolerate this condition.
To avoid unnecessary use of the battery where utility voltage is chronically low, set the low transfer point lower if the connected equipment can tolerate this condition.
230 V models only: Sets the output voltage of the UPS.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Maintenance, Transport, and Service
Maintenance, Transport, and Service Replacing the Battery Module This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the replacement procedure. Once the batteries are disconnected the connected equipment is not protected from power outages. Refer to the appropriate replacement battery user manual for battery module installation instructions. See your dealer or contact APC at www.apc.com for information on replacement battery modules. Be sure to deliver the spent battery(s) to a recycling facility or ship it to APC in the replacement battery packing material.
Service If the UPS requires service do not return it to the dealer. Follow these steps: 1. Review the problems discussed in Troubleshooting to eliminate common problems. 2. If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com. – Note the model number of the UPS, the serial number located on the back of the unit, and the date purchased. If you call APC Customer Support, a technician will ask you to describe the problem and attempt to solve it over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#). – If the UPS is under warranty, repairs are free. – Procedures for servicing or returning products may vary internationally. Refer to the APC Web site for country specific instructions. 3. Pack the UPS in its original packaging. If this is not available, refer to www.apc.com for information about obtaining a new set. – Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging. Damage sustained in transit is not covered under warranty. – Always DISCONNECT THE UPS BATTERY before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The battery may remain in the UPS. 4. Mark the RMA# on the outside of the package. 5. Return the UPS by insured, prepaid carrier to the address given to you by Customer Support.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
11
Troubleshooting
Troubleshooting Use this chart to solve minor UPS installation and operation problems. Refer to www.apc.com for assistance with complex UPS problems. Problem and/or Possible Cause
Solution
UPS will not turn on The battery is not connected properly. button not pushed.
Check that the battery connector is fully engaged. Press the
button once to power-up the UPS and connected equipment.
The UPS is not connected to utility power supply.
Check that the power cable from the UPS to the utility power supply is securely connected at both ends.
Very low or no utility voltage
Check the utility power supply to the UPS by plugging in a table lamp. If the light is very dim, have the utility voltage checked.
UPS will not turn off The UPS is experiencing an internal fault
Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.
UPS beeps occasionally Normal UPS operation when running on battery.
None: The UPS is protecting the connected equipment. Press the to silence this alarm.
button
UPS is not providing expected backup time The UPS battery(s) are weak due to a recent power outage or battery(s) are near the end of their service life.
Charge the battery(s). Batteries require recharging after extended outages. Batteries can wear faster when put into service often or when operated at elevated temperatures. If the battery(s) are near the end of their service life, consider replacing the battery(s) even if the replace battery LED is not yet illuminated.
All LEDs are illuminated and the UPS emits a constant beeping The UPS is experiencing an internal fault.
Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.
Front panel LEDs flash sequentially The UPS has been shut down remotely through software or an optional accessory card.
None: The UPS will restart automatically when utility power returns.
All LEDs are off and the UPS is plugged into a wall outlet The UPS is shut down or the battery is discharged from an extended outage. 12
None: The UPS will restart automatically when utility power is restored and the battery has a sufficient charge. Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Troubleshooting
Problem and/or Possible Cause
Solution
The Overload LED is illuminated and the UPS emits a sustained alarm tone The UPS is overloaded.
The connected equipment exceeds the specified “maximum load” as defined in Specifications on the APC Web site, www.apc.com. The alarm remains on until the overload is removed. Disconnect nonessential equipment from the UPS to eliminate the overload condition. The UPS continues to supply power as long as it is online and the circuit breaker does not trip; the UPS will not provide power from batteries in the event of a utility voltage interruption.
The Replace Battery/Battery Disconnected LED is illuminated The Replace Battery/Battery Disconnected LED flashes and a short beep is emitted every two seconds to indicate the battery is disconnected.
Check that the battery connectors are fully engaged.
Weak battery
Allow the battery to recharge for 24 hours and perform a self-test. If the problem persists after recharging, replace the battery.
Failure of a battery self-test: Replace Battery/Battery Disconnected LED illuminates and the UPS emits short beeps for one minute. The UPS repeats the alarm every five hours.
Allow the battery to recharge for 24 hours. Perform the self-test procedure to confirm the replace battery condition. The alarm stops and the LED clears if the battery passes the self-test. If the battery fails again, it must be replaced. The connected equipment is unaffected.
The Site Wiring Fault LED on the rear panel is illuminated (120 V model only) The UPS is plugged into an improperly wired utility power outlet.
Wiring faults detected include missing ground, hot-neutral polarity reversal, and overloaded neutral circuit. Contact a qualified electrician to correct the building wiring.
The input circuit breaker trips The connected equipment exceeds the specified “maximum load” as defined in Specifications on the APC Web site, www.apc.com.
Unplug all nonessential equipment from the UPS. Reset the circuit breaker.
The AVR Boost or AVR Trim LEDs are illuminated The system is experiencing very high or low utility voltage.
Have a qualified service personnel check your facility for electrical problems. If the problem persists, contact the utility company for further assistance.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
13
Troubleshooting
Problem and/or Possible Cause
Solution
There is no utility power There is no utility power and the UPS is off.
Use the cold start feature to supply power to the connected equipment front the UPS battery(s). Press and hold the button. There will be a short beep followed by a longer beep. Release the button during the second beep.
UPS operates on battery although line voltage exists The UPS input circuit breaker trips.
Unplug all nonessential equipment from the UPS. Reset the circuit breaker.
Your system is experiencing very high, low or distorted line voltage.
Move the UPS to a different outlet on a different circuit: Inexpensive fuel powered generators may distort the voltage. Test the input voltage with the utility voltage display, (see Operation). If acceptable to the connected equipment, reduce the UPS sensitivity.
Battery Charge and Load LEDs flash simultaneously The UPS has shut down. The internal temperature of the UPS has exceeded the allowable threshold for safe operation.
Check that the room temperature is within the specified limits for operation. Check that the UPS is properly installed, allowing for adequate ventilation. Allow the UPS to cool down. Restart the UPS. If the problem persists, contact APC at www.apc.com.
Diagnostic utility voltage All five LEDs are illuminated.
The line voltage is extremely high and should be checked by an electrician.
There is no LED illumination.
The line voltage is extremely low and should be checked by an electrician.
On Line LED There is no LED illumination.
The UPS is running on battery, or it must be turned on.
The LED is blinking.
The UPS is running an internal self-test.
14
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Regulatory and Warranty Information
Regulatory and Warranty Information Regulatory Agency Approvals and Radio Frequency Warnings FCC Compliance Notice
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy. If it is not installed and used in accordance with the instruction manual, it may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case users will be required to take whatever measures may be necessary to correct the interference at their own expense.
120 V models
R3A031 LISTED 42C2 E95463
230 V models N 394
geprüf te Sich erh eit
Limited Warranty American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply to equipment that has been damaged by accident, negligence, or misapplication or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. EXCEPT AS PROVIDED HEREIN, AMERICAN POWER CONVERSION MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser. EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL APC BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, APC is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
15
Regulatory and Warranty Information
Date of product declaration
16
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
Regulatory and Warranty Information
APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: •
Refer to the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. – www.apc.com/support/ Global support searching APC Knowledge Base and using e-support. • Contact an APC Customer Support center by telephone or e-mail. Local, country-specific centers: go to www.apc.com/support/contact for information. Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support.
Entire contents copyright 2005 American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited. APC, the APC logo, Smart-UPS, and PowerChute are trademarks of American Power Conversion Corporation. All other trademarks, product names, and corporate names are the property of their respective owners and are used for informational purposes only.
Smart-UPS XL 2200/3000 VA 120/230 VAC 3U Rack Mount User Manual
17
Size:Download
English
APC Smart-UPS®
750/1000/1500 VA
100/120/230 Vac
Apc back-ups be750g new model available, be850m2 The Back-UPS BE750G provides a variety of energy efficient features that make it the greenest battery backup in its class. Click here to learn more. The Back-UPS ES is operating normally. The Back-UPS ES can only operate on battery power for a limited amount of time. The unit will eventually turn off when the available battery power has been used. Allow the unit to recharge for 16 hours before expecting maximum runtime. The output waveform is designed for computers and computer-related.
2U Rack-Mount
Uninterruptible Power Supply
Introduction
The APC Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags, and surges from reaching your computer and other valuable electronic equipment. The UPS filters small utility line fluctuations and isolates your equipment from large disturbances by internally disconnecting from the utility line. The UPS provides continuous power from its internal battery until the utility line returns to safe levels or the battery is discharged.
1:INSTALLATION
Read the Safety Instruction sheet before installing the UPS.
Unpacking
Inspect the UPS upon receipt. APC designed robust packaging for your product. However, accidents and damage may occur during shipment. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents. The package contains the UPS, the front bezel, the rail kit, and a literature kit containing:
•Product documentation and safety information
•CD-ROM with additional user manual language support and safety information
•PowerChute® CD-ROM (120V/230V models only)
•Serial and USB communication cables
•Two IEC jumper cables and one plug adaptor (230V models only)
The UPS is shipped with the battery disconnected.
Rail Installation
Install the rails following instructions in the rail kit.
Mounting rails are supplied for the standard 4-post rack.Two-post racks require only the mounting brackets.
2 | Ear Mounting Locations: | |
1. | Standard | |
2. | Optional (1.4' setback) | |
3. |
13
1
Positioning the UPS
Place the UPS where it will be used. The UPS is heavy. Select a location sturdy enough to handle the weight.
Do not operate the UPS where there is excessive dust or the temperature and humidity are outside the specified limits.
0º40ºC (32º-104ºF)
PLACEMENT 0-95% Relative Humidity 2.5 cm (1 in.)
Mounting the UPS in a Rack
The UPS is heavy. To lighten it, you may remove the battery before mounting the unit in the rack (Steps 1 and 2).
Step 1 | Step 2 Caution: The battery is heavy. |
Step 3
Install the UPS at or near the bottom of the rack (Step 3).
Check to ensure the rack will not tip after installing the UPS into the rack.
2
Installing and Connecting the Battery and Attaching the Front Bezel
Step 1 | Step 2 |
Step 3 | Step 4 |
Connect battery plug to UPS. Tuck white battery cord into space above connector.
Connecting Equipment and Power to the UPS
100/120V Models
120V Model Only: Site wiring fault indicator
230V Models
3
1.Connect equipment to the UPS. Note: Do not connect a laser printer to the UPS. A laser printer draws significantly more power than other types of equipment and may overload the UPS.
2.Add any optional accessories to the Smart-Slot.
3.Using a power cord, plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
100V/120V models: The power cord is permanently attached to the rear panel of the UPS. The INPUT plug is a NEMA5-15P.
230V models: The power cord is supplied by the customer. Connect ground leads to the TVSS screw (optional). To make the connection, loosen the screw and connect the surge suppression device’s ground lead. Tighten the screw to secure the lead.
4.Turn on all connected equipment. To use the UPS as a master ON/OFF switch, be sure all connected equipment is switched ON. The equipment will not be powered until the UPS is turned on.
5.To power up the UPS press the button on the front panel.
•The UPS charges its battery when it is connected to utility power. The battery charges to 90% capacity during the first four hours of normal operation. Do not expect full battery run capability during this initial charge period.
•120V Models: Check the site wiring fault LED located on the rear panel. It lights up if the UPS is plugged into an improperly wired utility power outlet. Refer toTroubleshooting in this manual.
6.For additional computer system security, install PowerChute® Smart-UPS monitoring software.
BASICCONNECTORS
Serial Port | USB Port Power management software and interface kits can be used with the | ||
UPS. Use only interface kits supplied or approved by APC. |
Use an APC supplied cable to connect to the Serial Port. DO NOT use a standard serial interface cable since it is incompatible with the UPS connector.
Both Serial and USB Ports are provided. They cannot be used simultaneously.
TVSS Screw The UPS features a transient voltage surge-suppression (TVSS) screw for connecting the ground lead on surge suppression devices such as telephone and network line protectors.
When connecting grounding cable, disconnect the UPS from utility power.
4
Power On
Power Off
Online | The online LED illuminates when the UPS is supplying utility power to |
the connected equipment. If the LED is not lit, the UPS is either not | |
turned ON, or is supplying battery power. |
This LED illuminates to indicate the UPS is compensating for a high utility voltage.
This LED illuminates to indicate the UPS is compensating for a low utility voltage.
When the on battery power LED is lit the UPS is supplying battery power to the connected equipment. When on battery, the UPS sounds analarm—four beeps every 30 seconds.
The LED illuminates and the UPS emits a sustained alarm tone when an overload condition occurs.
5
Replace Battery
Battery
Disconnected
Automatic Self-Test
Manual Self-Test
Failure of a battery self-test causes the UPS to emit short beeps for one minute and thereplace battery LED illuminates. Refer toTroubleshooting in this manual.
The replace battery LED flashes and short beep is emitted every two seconds to indicate the battery is disconnected.
The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default).
During the self-test, the UPS briefly operates the connected equipment on battery.
If the UPS fails the self-test, thereplace battery LEDlights and immediately returns to online operation. The connected equipment is not affected by a failed test. Recharge the battery for 24 hours and perform anotherself-test. If it fails, the battery must be replaced.
Press and hold the button for a few seconds to initiate theself-test.
On Battery Operation
The Smart-UPS switches to battery operation automatically if the utility power fails. While running on battery, an alarm beeps four times every 30 seconds.
Press the button (front panel) to silence the UPS alarm (for the current alarm only). If the utility power does not return, the UPS continues to supply power to the connected equipment until the battery is exhausted.
If PowerChute® is not being used you must manually save your files and turn off the computer before the UPS fully discharges the battery.
DETERMININGONBATTERYRUNTIME
UPS battery life differs based on usage and environment. It is recommended that the battery/batteries be changed once every three years. See the APC web site, www.apc.com, for on battery run times.
6
3:USERCONFIGURABLEITEMS
Apc Back Ups 750 User Manual
NOTE: SETTINGS ARE MADE THROUGH SUPPLIEDPOWERCHUTE SOFTWARE OR OPTIONALSMARTSLOT
ACCESSORY CARDS.
FUNCTION | FACTORY | USERSELECTABLE | DESCRIPTION | ||||||
DEFAULT | CHOICES | ||||||||
Automatic | Every 14 days | Every 7 days | This function sets the interval | ||||||
(336 hours) | (168 hours), | at which the UPS will execute | |||||||
On Startup Only, No | a | ||||||||
ware manual for details. | |||||||||
UPS ID | UPS_IDEN | Up to eight characters to | Use this field to uniquely | ||||||
define the UPS | identify the UPS, (i.e. server | ||||||||
name or location) for network | |||||||||
management purposes. | |||||||||
Date of Last Battery Re- | Manufacture | Date of Battery Replace- | Reset this date when you | ||||||
placement | Date | ment | replace the battery module. | ||||||
mm/dd/yy | |||||||||
Minimum Capacity Before | 0 percent | 15, 25, 35, 50, 60, 75, 90 | The UPS will charge its bat- | ||||||
Return from Shutdown | percent | teries to the specified percent- | |||||||
age before return from a shut- | |||||||||
down. | |||||||||
Voltage Sensitivity | Brightly lit: UPS is set to | To change the UPS sensitiv- | |||||||
The UPS detects and reacts | high sensitivity. | ity, press the voltage sensitiv- | |||||||
Dimly lit: | ity button | (rear panel). | |||||||
to line voltage distortions | UPS is set to | ||||||||
Use a pointed object (such as | |||||||||
by transferring to battery | medium sensitivity. | ||||||||
a pen) to do so. | |||||||||
operation to protect the | Off: | UPS is set to | |||||||
connected equipment. | You can change the sensitiv- | ||||||||
low sensitivity. | |||||||||
Where power quality is | ity level through PowerChute | ||||||||
poor, the UPS may fre- | software. | ||||||||
quently transfer to battery | |||||||||
operation. If the connected | |||||||||
equipment can operate | |||||||||
normally under such condi- | |||||||||
tions, reduce the sensitivity | |||||||||
setting to conserve battery | |||||||||
capacity and service life. | |||||||||
Alarm Delay After Line | 5 second delay | 30 second delay, At Low | To avoid alarms for minor | ||||||
Fail | Battery Condition, No | power glitches, set the alarm | |||||||
delay. | |||||||||
Shutdown Delay | 20 seconds | 0, 60, 120, 240, 480, 720, | Sets the interval between the | ||||||
960 seconds | time when the UPS receives a | ||||||||
shutdown command and ac- | |||||||||
tual shutdown. |
7
NOTE: SETTINGS ARE MADE THROUGH SUPPLIEDPOWERCHUTE SOFTWARE OR OPTIONALSMARTSLOT
ACCESSORY CARDS.
FUNCTION | FACTORY | USERSELECTABLE | DESCRIPTION | |||||
DEFAULT | CHOICES | |||||||
Low Battery Warning. Tomtom driver error. | Brightly lit: Low battery | The low battery warning | ||||||
PowerChute interface | warning interval is about | beeps are continuous when | ||||||
two minutes. | two minutes of run time re- | |||||||
software provides auto- | ||||||||
Dimly lit: | Low battery | main. | ||||||
matic, unattended shut- | ||||||||
warning interval is about | You can change the warning | |||||||
down when approximately | ||||||||
five minutes. | ||||||||
two minutes (by default) of | interval default setting | |||||||
Off: | Low battery | |||||||
battery operated run time | through PowerChute soft- | |||||||
warning interval is about | ||||||||
remains. | ware. | |||||||
eight minutes. | ||||||||
Possible interval settings: | ||||||||
5, 7, 10, 12, 15, 18 min- | ||||||||
utes. | ||||||||
Synchronized | 0 seconds | 20, 60, 120, 240, 480, | The UPS will wait the speci- | |||||
Delay | 720, 960 seconds | fied time after the return of | ||||||
utility power before | ||||||||
(to avoid branch circuit over- | ||||||||
load). | ||||||||
High Transfer Point | 100V: | 100V: | To avoid unnecessary battery | |||||
108VAC | 110, 112, 114VAC | usage, set the high transfer | ||||||
120V: | 120V: | point higher if the utility volt- | ||||||
age is chronically high and | ||||||||
127VAC | 130, 133, 136VAC | the connected equipment is | ||||||
230V: | 230V: | known to work under this | ||||||
condition. | ||||||||
253VAC | 257, 261, 265VAC | |||||||
Low Transfer Point | 100V: | 100V: | Set the low transfer point | |||||
92VAC | 86, 88, 90VAC | lower if the utility voltage is | ||||||
120V: | 120V: | chronically low and the con- | ||||||
nected equipment can tolerate | ||||||||
106VAC | 97, 100, 103VAC | this condition. | ||||||
230V: | 230V: | |||||||
208VAC | 196, 200, 204VAC |
8